PowerFit 500A Set-Screw Connector: Conductor Axial Pull-Out Test

SEMT Report Nos. 2026JC (KP) 020 & 021Test dates: 2026-11-04 & 2026-11-09Reference: IEC 60947-7-1:2025

Axial pull-out testing of PowerFit 500A Line Source and Line Drain set-screw terminals assembled with 150 mm² copper conductors. Both configurations passed the specified 427 N load held for 60 seconds without conductor slippage.

Test setup

Product rating
500A
Conductor cross-section
150 mm²
Specified axial load
427 N
Load hold time
60 s

Report assessment

Line Source
PASS
Line Drain
PASS
Source complete pull-out
5,229 N
Drain complete pull-out
5,617 N

01 Measured results

Line Source conductor
# Test item Force (N) Time (s) Result
1 Specified load verification 427 60 PASS, no slippage
2 Initial slippage 5,115 201 —
3 Complete pull-out 5,229 259 —
Line Drain conductor
# Test item Force (N) Time (s) Result
1 Specified load verification 427 60 PASS, no slippage
2 Initial slippage 4,661 186 —
3 Complete pull-out 5,617 267 —

02 Evaluation summary

Specified load verification
Criterion Assessment
Apply 427 N axial tensile force to the 150 mm² copper conductor for 1 min; verify no conductor slippage or pull-out. PASS

Test reference and scope

The test refers to IEC 60947-7-1:2025, Clause 9.3.3.3 and Table 2. The standard is used solely as a test reference and does not imply compliance of the complete connector.

03 Test curves

PowerFit 500A Line Source conductor axial pull-out test curve
Figure 1: Line Source conductor test curve
PowerFit 500A Line Drain conductor axial pull-out test curve
Figure 2: Line Drain conductor test curve

04 Tested samples and equipment

Tested samples
Item Part number Configuration
1 PFLS-S150M40A PowerFit 500A Line Source set-screw conductor assembled with 150 mm² cable
2 PFLD-S150M40A PowerFit 500A Line Drain set-screw conductor assembled with 150 mm² cable
Testing equipment
Instrument Calibration date
Universal testing machine 2026-07-13

05 Purpose and scope

Purpose

To evaluate the mechanical connection reliability of PowerFit 500A set-screw line conductors, verify the axial retention of conductors installed on 150 mm² cables, and record tensile forces during initial slippage and complete pull-out.

Scope

This test applies to PowerFit 500A set-screw connector terminals installed on 150 mm² copper conductors. Axial tensile force is applied to evaluate conductor clamping and retention performance.

Acceptance statement

With reference to IEC 60947-7-1:2025, Clause 9.3.3.3 and Table 2, acceptance is based on the absence of conductor slippage or pull-out under the specified axial tensile load. Forces at initial slippage and complete pull-out are also recorded.