400A K-LOK Short-Circuit Withstand Test

Intertek Report No. 2608B1785SHA-001Test period: 2026-09-10 ~ 2026-11-03UL 508:2024 Ed.19 · Clause 52

Short-circuit withstand testing of K-LOK 400A single-pole cam-type connectors at 600 V AC and 35 kA for 60 ms (3 cycles). The in-line mating configuration passed the acceptance criteria in UL 508, Table 56.1.

Test setup

Test voltage
600 V AC
Short-circuit test current
35 kA
Energization duration
60 ms (3 cycles)
Connected cable
AWG 4/0 Type W single-conductor cable

Report assessment

In-line pair
PASS
Tested configuration
In-line male + in-line female
Acceptance criteria
Table 56.1 (a)–(e)
Report date
2026-11-03

01 Measured results

Acceptance criteria and results
# Acceptance criterion Result
a The solid AWG wire connected between the live pole and enclosure shall not open. PASS
b The door or cover shall not be blown open and shall remain openable. Openings caused by enclosure deformation shall comply with 7.17.1 for accessibility of live parts under normal operating conditions. PASS
c Conductors and terminal connectors shall not be damaged and no conductor shall pull out. Bus bars, insulators and connectors, including stab-in assemblies, shall not be damaged; bus bars shall not shift or pull out of mounts or terminals. PASS
d Insulating bases shall not break or crack to an extent that impairs the integrity of live-part mounting. PASS
e Ejection of parts or any risk of fire shall not occur. PASS

02 Evaluation summary

Short-circuit withstand verification
Criterion Assessment
With reference to UL 508:2024 Ed.19 Clause 52, a full voltage of 600 V and a prospective short-circuit current of 35 kA were applied for 3 cycles (60 ms, continuous energization, no interval), assessed against criteria (a)–(e) of UL 508, Table 56.1. PASS

03 Tested samples

Tested mating configuration
Item Product part number Configuration
1 KL-400LMBK × KL-400LFBK In-line male + in-line female pair, assembled with AWG 4/0 Type W single-conductor cable

04 Test parameters and conditions

Test conditions
Parameter Condition
Test voltage 600 V AC
Short-circuit test current 35 kA
Energization duration 60 ms (3 cycles)
Energization mode Continuous, without interruption
Connected cable AWG 4/0 Type W single-conductor cable

05 Purpose, scope and test basis

Purpose

To evaluate the short-circuit withstand capability of K-LOK 400A single-pole cam-type connectors under fault conditions — verifying no risk of fire, discharge of parts, or exposure of live parts at 600 V / 35 kA prospective short-circuit current — and to assess acceptance against the criteria of UL 508, Table 56.1.

Scope

This test applies to K-LOK 400A single-pole cam-type connectors, in-line versions, each assembled with AWG 4/0 Type W single-conductor cable, tested as in-line male + in-line female.

Test basis and acceptance statement

This test was conducted in accordance with UL 508:2024 Ed.19, Clause 52. Acceptance is based on criteria (a)–(e) of UL 508, Table 56.1. The standard serves solely as the test basis for this short-circuit withstand verification and does not constitute UL 508 certification of the complete connector series.

Test report