400A K-LOK Short-Circuit Withstand Test
Short-circuit withstand testing of K-LOK 400A single-pole cam-type connectors at 600 V AC and 35 kA for 60 ms (3 cycles). The in-line mating configuration passed the acceptance criteria in UL 508, Table 56.1.
Test setup
- Test voltage
- 600 V AC
- Short-circuit test current
- 35 kA
- Energization duration
- 60 ms (3 cycles)
- Connected cable
- AWG 4/0 Type W single-conductor cable
Report assessment
- In-line pair
- PASS
- Tested configuration
- In-line male + in-line female
- Acceptance criteria
- Table 56.1 (a)–(e)
- Report date
- 2026-11-03
01 Measured results
| # | Acceptance criterion | Result |
|---|---|---|
| a | The solid AWG wire connected between the live pole and enclosure shall not open. | PASS |
| b | The door or cover shall not be blown open and shall remain openable. Openings caused by enclosure deformation shall comply with 7.17.1 for accessibility of live parts under normal operating conditions. | PASS |
| c | Conductors and terminal connectors shall not be damaged and no conductor shall pull out. Bus bars, insulators and connectors, including stab-in assemblies, shall not be damaged; bus bars shall not shift or pull out of mounts or terminals. | PASS |
| d | Insulating bases shall not break or crack to an extent that impairs the integrity of live-part mounting. | PASS |
| e | Ejection of parts or any risk of fire shall not occur. | PASS |
02 Evaluation summary
| Criterion | Assessment |
|---|---|
| With reference to UL 508:2024 Ed.19 Clause 52, a full voltage of 600 V and a prospective short-circuit current of 35 kA were applied for 3 cycles (60 ms, continuous energization, no interval), assessed against criteria (a)–(e) of UL 508, Table 56.1. | PASS |
03 Tested samples
| Item | Product part number | Configuration |
|---|---|---|
| 1 | KL-400LMBK × KL-400LFBK | In-line male + in-line female pair, assembled with AWG 4/0 Type W single-conductor cable |
04 Test parameters and conditions
| Parameter | Condition |
|---|---|
| Test voltage | 600 V AC |
| Short-circuit test current | 35 kA |
| Energization duration | 60 ms (3 cycles) |
| Energization mode | Continuous, without interruption |
| Connected cable | AWG 4/0 Type W single-conductor cable |
05 Purpose, scope and test basis
Purpose
To evaluate the short-circuit withstand capability of K-LOK 400A single-pole cam-type connectors under fault conditions — verifying no risk of fire, discharge of parts, or exposure of live parts at 600 V / 35 kA prospective short-circuit current — and to assess acceptance against the criteria of UL 508, Table 56.1.
Scope
This test applies to K-LOK 400A single-pole cam-type connectors, in-line versions, each assembled with AWG 4/0 Type W single-conductor cable, tested as in-line male + in-line female.
Test basis and acceptance statement
This test was conducted in accordance with UL 508:2024 Ed.19, Clause 52. Acceptance is based on criteria (a)–(e) of UL 508, Table 56.1. The standard serves solely as the test basis for this short-circuit withstand verification and does not constitute UL 508 certification of the complete connector series.
Test report
Intertek Report No. 2608B1785SHA-001
Intertek Testing Services (Shanghai FTZ) Co., Ltd.
Test period: 2026-09-10 ~ 2026-11-03
Report date: 2026-11-03 · All samples passed