660A ITT Powerlock Line Source to KUPO PowerFit Panel Drain: Interconnection Test
Temperature-rise test of an ITT POWERLOCK 660 A line source mated with a KUPO POWERFIT 750 A panel drain, carrying 664 A for 3 hours. The ITT side uses 500 MCM (approximately 253 mm²) cable; the KUPO side uses 400 mm² cable.
Test setup
- Test current
- 664A
- Cable cross-section
- KUPO 400 mm² / ITT 500 MCM (≈253 mm²)
- Ambient temperature
- 19.2°C
- Test duration
- 3hours
Report assessment
- Maximum recorded temperature rise
- 27.0°C
- Maximum outer-casing temperature rise
- 14.5°C
- Maximum allowable temperature
- 125°C
- Report result
- PASS
01 Measured results
Test current: 664A · Ambient: 19.2°C · Duration: 3 hours
Temperature rise by measurement point
ΔT in °C · chart scale: 0 to 70°C
| # | Measurement point | Ambient Ta (°C) |
Measured T (°C) |
Rise ΔT (°C) |
Load (A) |
|---|---|---|---|---|---|
| 1 | ITT POWERLOCK line source terminal-lug connection | 19.2 | 45.3 | 26.1 | 664 |
| 2 | ITT POWERLOCK line source conductor | 19.2 | 46.2 | 27.0 | 664 |
| 3 | ITT POWERLOCK line source outer casing | 19.2 | 31.1 | 11.9 | 664 |
| 4 | KUPO POWERFIT panel drain outer casing | 19.2 | 33.7 | 14.5 | 664 |
| 5 | KUPO POWERFIT panel drain conductor | 19.2 | 45.3 | 26.1 | 664 |
| 6 | LINE SOURCE cable copper core | 19.2 | 44.8 | 25.6 | 664 |
| 7 | LINE SOURCE cable jacket | 19.2 | 39.4 | 20.2 | 664 |
Rise (ΔT) = measured temperature (T) − ambient temperature (Ta). Source: SEMT test report.
02 Evaluation summary
| Criterion | Result | Assessment |
|---|---|---|
| Maximum allowable temperature | 125°C | Compliant |
| Maximum recorded temperature rise of contacts | 27.0°C | PASS |
| Maximum recorded temperature rise of outer casing | 14.5°C | PASS |
| Temperature rise within IEC/EN 61984:2009 / BS EN 61984:2009 limits | Within limits | PASS |
| Cross-brand interconnection assessment | Thermally stable | PASS |
Interconnection conclusion
The KUPO POWERFIT and ITT Powerlock connectors were run at 660–675A for 3 hours. The report assesses the temperature rise at every critical measurement point as within the applicable requirements of IEC/EN 61984:2009 / BS EN 61984:2009, and records stable thermal performance for the tested interconnection.
PASS is the report’s assessment for this tested assembly and setup.
03 Test conditions
| Parameter | Condition and value |
|---|---|
| Ambient temperature | 19.2°C |
| Test current | 664A (held at 660–675A) |
| Test voltage | 0.374V |
| Test frequency | 50 Hz |
| Test duration | 3 hours |
04 Tested samples and equipment
| Item | Part number | Configuration |
|---|---|---|
| 1 | NLDFT-1-BN-L-C185-M40B | ITT POWERLOCK 660 A line source, assembled with 500 MCM (approximately 253 mm²) cable |
| 2 | PFPD-1BN-T7 | KUPO POWERFIT 750 A panel drain, assembled with 400 mm² cable |
| Instrument | Calibration date |
|---|---|
| High-current generator | 2026-07-28 |
| Multi-channel temperature tester | 2026-07-12 |
| Clamp-on multimeter | 2026-07-12 |
05 Purpose and scope
Purpose
To evaluate the current-carrying capability and temperature-rise performance of an interconnection between KUPO POWERFIT and ITT Powerlock connectors under rated current conditions, and to assess its thermal stability during continuous operation.
Scope
The test measures temperatures at critical points of the mated assembly, including the cable lug connection, conductors, connector housings and cable, to assess the thermal performance of a cross-brand connector interconnection.
Acceptance statement
Under the specified test conditions, the assembly was energized at 660–675A for 3 hours. The temperature rise at each critical point was measured and assessed against the allowable limits of IEC/EN 61984:2009 / BS EN 61984:2009.
Source report
SEMT Report No. 2026JC (KP) 023
Test date: 2026-11-18 ~ 2026-11-19