660A ITT Powerlock Line Source to KUPO PowerFit Panel Drain: Interconnection Test

SEMT Report No. 2026JC (KP) 023 Test date: 2026-11-18 ~ 2026-11-19 Standard: IEC/EN 61984:2009 / BS EN 61984:2009

Temperature-rise test of an ITT POWERLOCK 660 A line source mated with a KUPO POWERFIT 750 A panel drain, carrying 664 A for 3 hours. The ITT side uses 500 MCM (approximately 253 mm²) cable; the KUPO side uses 400 mm² cable.

Test setup

Test current
664A
Cable cross-section
KUPO 400 mm² / ITT 500 MCM (≈253 mm²)
Ambient temperature
19.2°C
Test duration
3hours

Report assessment

Maximum recorded temperature rise
27.0°C
Maximum outer-casing temperature rise
14.5°C
Maximum allowable temperature
125°C
Report result
PASS

01 Measured results

Test current: 664A · Ambient: 19.2°C · Duration: 3 hours

Measured results · 7 measurement points
# Measurement point Ambient
Ta (°C)
Measured
T (°C)
Rise
ΔT (°C)
Load
(A)
1 ITT POWERLOCK line source terminal-lug connection 19.2 45.3 26.1 664
2 ITT POWERLOCK line source conductor 19.2 46.2 27.0 664
3 ITT POWERLOCK line source outer casing 19.2 31.1 11.9 664
4 KUPO POWERFIT panel drain outer casing 19.2 33.7 14.5 664
5 KUPO POWERFIT panel drain conductor 19.2 45.3 26.1 664
6 LINE SOURCE cable copper core 19.2 44.8 25.6 664
7 LINE SOURCE cable jacket 19.2 39.4 20.2 664

Rise (ΔT) = measured temperature (T) − ambient temperature (Ta). Source: SEMT test report.

02 Evaluation summary

Criterion Result Assessment
Maximum allowable temperature 125°C Compliant
Maximum recorded temperature rise of contacts 27.0°C PASS
Maximum recorded temperature rise of outer casing 14.5°C PASS
Temperature rise within IEC/EN 61984:2009 / BS EN 61984:2009 limits Within limits PASS
Cross-brand interconnection assessment Thermally stable PASS

Interconnection conclusion

The KUPO POWERFIT and ITT Powerlock connectors were run at 660–675A for 3 hours. The report assesses the temperature rise at every critical measurement point as within the applicable requirements of IEC/EN 61984:2009 / BS EN 61984:2009, and records stable thermal performance for the tested interconnection.

PASS is the report’s assessment for this tested assembly and setup.

03 Test conditions

Parameter Condition and value
Ambient temperature 19.2°C
Test current 664A (held at 660–675A)
Test voltage 0.374V
Test frequency 50 Hz
Test duration 3 hours

04 Tested samples and equipment

Tested samples
Item Part number Configuration
1 NLDFT-1-BN-L-C185-M40B ITT POWERLOCK 660 A line source, assembled with 500 MCM (approximately 253 mm²) cable
2 PFPD-1BN-T7 KUPO POWERFIT 750 A panel drain, assembled with 400 mm² cable
Testing equipment
Instrument Calibration date
High-current generator 2026-07-28
Multi-channel temperature tester 2026-07-12
Clamp-on multimeter 2026-07-12

05 Purpose and scope

Purpose

To evaluate the current-carrying capability and temperature-rise performance of an interconnection between KUPO POWERFIT and ITT Powerlock connectors under rated current conditions, and to assess its thermal stability during continuous operation.

Scope

The test measures temperatures at critical points of the mated assembly, including the cable lug connection, conductors, connector housings and cable, to assess the thermal performance of a cross-brand connector interconnection.

Acceptance statement

Under the specified test conditions, the assembly was energized at 660–675A for 3 hours. The temperature rise at each critical point was measured and assessed against the allowable limits of IEC/EN 61984:2009 / BS EN 61984:2009.

Source report