800A PHASE 3 PowerSafe Panel Source to KUPO PowerFit Line Drain: Interconnection Test

SEMT Report No. 2026JC (KP) 019 Test date: 2026-10-30 Standard: IEC/EN 61984:2009 / BS EN 61984:2009

Temperature-rise test of a PHASE 3 POWERSAFE 800 A panel source mated with a KUPO POWERFIT 800 A line drain, using 400 mm² cable and carrying 805 A for 3 hours.

Test setup

Test current
805A
Cable cross-section
400 mm²
Ambient temperature
24.6°C
Test duration
3hours

Report assessment

Maximum contact temperature rise
44.4°C
Maximum outer-casing temperature rise
26.5°C
Maximum allowable temperature
125°C
Report result
PASS

01 Measured results

Test current: 805A · Ambient: 24.6°C · Duration: 3 hours

Measured results · 7 measurement points
# Measurement point Ambient
Ta (°C)
Measured
T (°C)
Rise
ΔT (°C)
Load
(A)
1 PHASE 3 POWERSAFE panel source terminal-lug connection 24.6 66.8 42.2 805
2 PHASE 3 POWERSAFE panel source conductor 24.6 69.0 44.4 805
3 PHASE 3 POWERSAFE panel source outer casing 24.6 49.0 24.4 805
4 KUPO POWERFIT line drain outer casing 24.6 51.1 26.5 805
5 KUPO POWERFIT line drain conductor 24.6 68.2 43.6 805
6 LINE DRAIN cable core 24.6 69.2 44.6 805
7 LINE DRAIN cable jacket 24.6 59.7 35.1 805

Rise (ΔT) = measured temperature (T) − ambient temperature (Ta). Source: SEMT test report.

02 Evaluation summary

Criterion Result Assessment
Maximum allowable temperature 125°C Compliant
Maximum recorded temperature rise of contacts 44.4°C PASS
Maximum recorded temperature rise of outer casing 26.5°C PASS
Temperature rise within IEC/EN 61984:2009 / BS EN 61984:2009 limits Within limits PASS
Cross-brand interconnection assessment Thermally stable PASS

Interconnection conclusion

The KUPO POWERFIT and PHASE 3 PowerSafe connectors were run at 800–815 A for 3 hours. The report assesses the temperature rise at every critical measurement point as within the applicable requirements of IEC/EN 61984:2009 / BS EN 61984:2009, and records stable thermal performance for the tested interconnection.

PASS is the report’s assessment for this tested assembly and setup.

03 Test conditions

Parameter Condition and value
Ambient temperature 24.6°C
Test current 805A
Test voltage 0.374V
Test frequency 50 Hz
Test duration 3 hours

04 Tested samples and equipment

Tested samples
Item Part number Configuration
1 SPS-2-BN-T8 PHASE 3 POWERSAFE 800 A panel source, assembled with 400 mm² cable
2 PFLD-1BN-C300-C400-M40/M50 KUPO POWERFIT 800 A line drain, assembled with 400 mm² cable
Testing equipment
Instrument Calibration date
High-current generator 2026-07-28
Multi-channel temperature tester 2026-07-12
Clamp-on multimeter 2026-07-12

05 Purpose and scope

Purpose

To evaluate the current-carrying capability and temperature-rise performance of an interconnection between KUPO POWERFIT and PHASE 3 PowerSafe connectors under rated current conditions, and to assess its thermal stability during continuous operation.

Scope

The test measures temperatures at critical points of the mated assembly, including the cable lug connection, conductors, connector housings and cable, to assess the thermal performance of a cross-brand connector interconnection.

Acceptance statement

Under the specified test conditions, the assembly was energized at 800–815 A for 3 hours. The temperature rise at each critical point was measured and assessed against the allowable limits of IEC/EN 61984:2009 / BS EN 61984:2009.

Source report