800A POWERFIT Panel Drain to PHASE 3 PowerSafe Line Source: Interconnection Test

SEMT Report No. 2026JC (KP) 021 Test date: 2026-11-10 ~ 2026-11-11 Standard: IEC/EN 61984:2009 / BS EN 61984:2009

Temperature-rise test of a KUPO POWERFIT 800A panel drain mated with a PHASE 3 PowerSafe 800A line source, carrying 805A on 400 mm² cable for 3 hours.

Test setup

Test current
805A
Cable cross-section
400 mm²
Ambient temperature
19.3°C
Test duration
3hours

Report assessment

Maximum recorded temperature rise
43.8°C
Maximum outer-casing temperature rise
19.0°C
Maximum allowable temperature
125°C
Report result
PASS

01 Measured results

Test current: 805A · Ambient: 19.3°C · Duration: 3 hours

Measured results · 7 measurement points
# Measurement point Ambient
Ta (°C)
Measured
T (°C)
Rise
ΔT (°C)
Load
(A)
1 Panel Drain-Lug Connection (POWERFIT) 19.3 60.2 40.9 805
2 Panel Drain Conductor (POWERFIT) 19.3 63.1 43.8 805
3 Panel Drain Outer Casing (POWERFIT) 19.3 38.3 19.0 805
4 Line Source Outer Casing (PHASE 3 PowerSafe) 19.3 32.0 12.7 805
5 Line Source Conductor (PHASE 3 PowerSafe) 19.3 59.0 39.7 805
6 Line Source Cable Core 19.3 59.0 39.7 805
7 Line Source Cable Jacket 19.3 49.1 29.8 805

Rise (ΔT) = measured temperature (T) − ambient temperature (Ta). Source: SEMT test report.

02 Evaluation summary

Criterion Result Assessment
Maximum allowable temperature 125°C Compliant
Maximum recorded temperature rise of contacts 43.8°C PASS
Maximum recorded temperature rise of outer casing 19.0°C PASS
Temperature rise within IEC/EN 61984:2009 / BS EN 61984:2009 limits Within limits PASS
Cross-brand interconnection assessment Thermally stable PASS

Interconnection conclusion

The KUPO POWERFIT and PHASE 3 PowerSafe connectors were run at 805A for 3 hours. The report assesses the temperature rise at every critical measurement point as within the applicable requirements of IEC/EN 61984:2009 / BS EN 61984:2009, and records stable thermal performance for the tested interconnection.

PASS is the report’s assessment for this tested assembly and setup.

03 Test conditions

Parameter Condition and value
Ambient temperature 19.3°C
Test current 805A
Test voltage 0.378V
Test frequency 50 Hz
Test duration 3 hours

04 Tested samples and equipment

Tested samples
Item Part number Configuration
1 PFPD-3GY-T8 KUPO POWERFIT 800A panel drain connector, assembled with 400 mm² cable
2 SLS-2-BK-C300-M50 PHASE 3 PowerSafe 800A line source connector, assembled with 400 mm² cable
Testing equipment
Instrument Calibration date
High-current generator 2026-07-28
Multi-channel temperature tester 2026-07-12
Clamp-on multimeter 2026-07-12

05 Purpose and scope

Purpose

To evaluate the current-carrying capability and temperature-rise performance of an interconnection between KUPO POWERFIT and PHASE 3 PowerSafe connectors under rated current conditions, and to assess its thermal stability during continuous operation.

Scope

The test measures temperatures at critical points of the mated assembly, including the cable lug connection, conductors, connector housings and cable, to assess the thermal performance of a cross-brand connector interconnection.

Acceptance statement

Under the specified test conditions, the assembly was energized at 805A for 3 hours. The temperature rise at each critical point was measured and assessed against the allowable limits of IEC/EN 61984:2009 / BS EN 61984:2009.

Source report