POWERFIT 500A Temperature Rise Test Data

POWERFIT 500A

Recorded test current
503A
Cable cross-section
150mm²
Ambient temperature
26.3°C
Test duration
3 hours

POWERFIT 500A test results

Test date:

Test current
503A
Ambient
26.3°C
Cable
150mm²
Test voltage
0.311V
Frequency / duration
50 Hz / 3 hours

Why the report records PASS

The report assesses the recorded temperature rises as within its cited IEC / BS EN 61984:2009 acceptance limits under these test conditions.

The highest measured temperature was 83.2°C at 26.3°C ambient, below the report’s listed 125°C maximum allowable temperature. The 125°C figure is an absolute temperature, not a temperature-rise limit.

PASS is the report’s assessment for this tested assembly and setup.

Measured results · 7 measurement points
# Measurement point Ambient
Ta (°C)
Measured
T (°C)
Rise
ΔT (°C)
Load
(A)
1 Panel Drain-Lug Connection 26.3 51.8 51.8 503
2 Panel Drain Conductor 26.3 75.9 49.8 503
3 Panel Drain Outer Casing 26.3 55.0 28.7 503
4 Line Source Outer Casing 26.3 44.1 17.8 503
5 Line Source Conductor 26.3 83.2 56.9 503
6 Line Source Cable Core 26.3 79.0 52.7 503
7 Cable Jacket 26.3 75.9 49.6 503

Source: KUPO test report, Section 08. Rise = Measured − Ambient.

Download the 500A test report (PDF, 4 pages)

Tested samples

PFPD-2BK-T5
POWERFIT 500A panel drain connector assembled with 150mm² cable

PFLS-2BK-S150M40A
POWERFIT 500A line source screw termination connector assembled with 150mm² cable

Test scope and interpretation

How should the 125°C figure be read?

The evaluation summaries list 125°C as “Maximum Allowable Temperature.” It is not labeled as a 125°C temperature-rise limit.

Why are there no temperature-versus-time curves?

The reports include the curves as images only, so this page charts the tabulated values from Section 08. The original curves are in the downloadable reports.

Source reports

POWERFIT 500A

SEMT Report No. 2026JC (KP) 013
Test date: 2026-10-20

Download 500A report (PDF)

Chinese and English · 4 pages.
Test conditions, measured results and original curve.

Original report: POWERFIT 500A line source to panel drain temperature-rise test (Chinese and English)