POWERFIT 500A Temperature Rise Test Data
POWERFIT 500A
- Recorded test current
- 503A
- Cable cross-section
- 150mm²
- Ambient temperature
- 26.3°C
- Test duration
- 3 hours
POWERFIT 500A test results
Test date:
- Test current
- 503A
- Ambient
- 26.3°C
- Cable
- 150mm²
- Test voltage
- 0.311V
- Frequency / duration
- 50 Hz / 3 hours
Temperature rise by measurement point
ΔT in °C · shared chart scale: 0 to 70°C
Why the report records PASS
The report assesses the recorded temperature rises as within its cited IEC / BS EN 61984:2009 acceptance limits under these test conditions.
The highest measured temperature was 83.2°C at 26.3°C ambient, below the report’s listed 125°C maximum allowable temperature. The 125°C figure is an absolute temperature, not a temperature-rise limit.
PASS is the report’s assessment for this tested assembly and setup.
| # | Measurement point | Ambient Ta (°C) |
Measured T (°C) |
Rise ΔT (°C) |
Load (A) |
|---|---|---|---|---|---|
| 1 | Panel Drain-Lug Connection | 26.3 | 51.8 | 51.8 | 503 |
| 2 | Panel Drain Conductor | 26.3 | 75.9 | 49.8 | 503 |
| 3 | Panel Drain Outer Casing | 26.3 | 55.0 | 28.7 | 503 |
| 4 | Line Source Outer Casing | 26.3 | 44.1 | 17.8 | 503 |
| 5 | Line Source Conductor | 26.3 | 83.2 | 56.9 | 503 |
| 6 | Line Source Cable Core | 26.3 | 79.0 | 52.7 | 503 |
| 7 | Cable Jacket | 26.3 | 75.9 | 49.6 | 503 |
Source: KUPO test report, Section 08. Rise = Measured − Ambient.
Download the 500A test report (PDF, 4 pages)
Tested samples
PFPD-2BK-T5
POWERFIT 500A panel drain connector assembled with 150mm² cable
PFLS-2BK-S150M40A
POWERFIT 500A line source screw termination connector assembled with 150mm² cable
Test scope and interpretation
How should the 125°C figure be read?
The evaluation summaries list 125°C as “Maximum Allowable Temperature.” It is not labeled as a 125°C temperature-rise limit.
Why are there no temperature-versus-time curves?
The reports include the curves as images only, so this page charts the tabulated values from Section 08. The original curves are in the downloadable reports.
Source reports
POWERFIT 500A
SEMT Report No. 2026JC (KP) 013
Test date: 2026-10-20
Chinese and English · 4 pages.
Test conditions, measured results and original curve.
Original report: POWERFIT 500A line source to panel drain temperature-rise test (Chinese and English)